Add to Cart
Hotel Air Conditioning Equipment Air Energy Heat Pump 75Kw ~90Kw Per Set
Quick information
Model data/ Parameter of commercial air-source heat pump
Model | SLNC-075Ycode name.pdf | |||
Compressor capacity | 25HP | |||
Function | Heating and Cooling | |||
Electricity | 380V-3N-50Hz | |||
Working conditions | ℃ | -25~+45 | ||
Data | Heata | Nominal capacity | KW | 44.5 |
Input power | KW | 18.3 | ||
COP | / | 2.4 | ||
Heating IPLV(H) | 2.7 | |||
Coolb | Nominal capacity | KW | 62 | |
Input power | KW | 20.7 | ||
COP | / | 3 | ||
Cooling IPLV(C) | 2.7 | |||
A7W35c | KW/COP | 75.0/4.2 | ||
A2W35 | KW/COP | 62.5/3.20 | ||
A-7W35 | KW/COP | 50/2.9 | ||
A-15W55 | KW/COP | 45.5 /1.97 | ||
A-20W45 | KW/COP | 37.4/2.04 | ||
Max. running currency | A | 56 | ||
Compressor quantity | set | 2 | ||
Refrigerant/charging quantity kg | / | R22/15*2 | ||
Air blow type | / | Top | ||
Water pipe diameter | mm | 50 | ||
Rating flow | m³/h | 12.6 | ||
Water side pressure loss | kPa | ≤45 | ||
Noise level | dB(A) | 62 | ||
Overall dimensions(L×W×H) | mm | 2100×1100×2080 | ||
Weight | kg | 730 |
A7W35 working condition: inlet air temperature 7℃, outlet water temperature 35℃
a: Nominal heating conditions: ambient dry bulb temperature-12℃, wet bulb temperature-14℃, outlet water temperature 41℃, water flow 0.172 * nominal
Yushen Products Advantages
Our service