Add to Cart
Low Environmental temperature Air Source Heat Pump Heating System
Difference of normal ASHP and low environmental temperature ASHP
1. working conditions
Normal ASHP work when environmental temperature is above -10C, in lower temeprature, normal ASHP has problem in defrosting,and compressor
Low temperature ASHP could work well even temperature is low to -25C
2.Technology
Low temperature ASHP could defrost very fast , 90 seconds;
Low temperature ASHP has Jet booster compressor,compressor take use of refrigerant more efficiently
heating is stable in low temperature environment.
Air source heat pump heating project Introduce
Project location | E 107 N 40 Climate:lowest -22C in winter |
Heating area | 70000M2 |
Quantity of air-source heat pump | 55 sets |
Model | SDNA-075Y(25HP) |
System design |
ultra low temperature air source heat pump+radiator
|
Control | Central heating station automatic control |
ASHP model in this project
Model | SDNA-075Ycode name.pdf | |||
Compressor capacity | 25HP | |||
Function | Heat | |||
Electricity | 380V 3N-50Hz | |||
Working conditions | ℃ | -25~+45 | ||
Data | Heata | Nominal capacity | KW | 44.5 |
Input power | KW | 18.3 | ||
COP | / | 2.4 | ||
Heating IPLV(H) | 2.7 | |||
A7W35c | KW/COP | 75.0/4.2 | ||
A2W35 | KW/COP | 62.5/3.20 | ||
A-7W35 | KW/COP | 52.5/3.0 | ||
A-15W55 | KW/COP | 45.5 /1.97 | ||
A-20W45 | KW/COP | 37.4/2.04 | ||
Max. running currency | A | 56 | ||
Compressor quantity | set | 2 | ||
Refrigerant/charging quantity kg | / | R22/10*2 | ||
Air blow type | / | Top | ||
Water pipe diameter | mm | 50 | ||
Rating flow | m³/h | 12.6 | ||
Water side pressure loss | kPa | ≤45 | ||
Noise level | dB(A) | 62 | ||
Overall dimensions(L×W×H) | mm | 2100×1100×2080 | ||
Weight | kg | 730 |
Yushen Products Advantages
The four-row tube V-shaped arrangement has high heat exchange efficiency and uniform wind speed distribution.