Shandong Yushen Energy Technology Co., Ltd.

Shandong Yushen Energy Technology Co., Ltd.

Manufacturer from China
Active Member
7 Years
Home / Products / Central Air Conditioner Heat Pump /

Low Noise Central Air Conditioner Heat Pump Cooling And Heating Function

Contact Now
Shandong Yushen Energy Technology Co., Ltd.
City:shanghai
Province/State:shanghai
Country/Region:china
Contact Person:MissSilvia
Contact Now

Low Noise Central Air Conditioner Heat Pump Cooling And Heating Function

Ask Latest Price
Brand Name :Yushen
Model Number :017Y~075Y
Certification :CCC, ISO, CQC
Place of Origin :China
MOQ :1 set
Price :negotiable
Payment Terms :T/T
Supply Ability :10 sets/day
Delivery Time :1-2weeks
Packaging Details :Reinforced Carton box with wooden tray
Name :Central Air Conditioner Heat Pump
Compressor capacity :6Hp ~25HP
Function :Cooling And Heating Function
Noise level :62dba
Feature :Low Noise
Electricity :380V-3P-50hz
Working conditions :-25C ~+45C
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Low Noise Central Air Conditioner Heat Pump Cooling And Heating Function

Central Air Conditioner Heat Pump Features

Central Air Conditioner Heat Pump (ASHP) is a system which transfers heat from outside to inside a building, or vice versa. Under the principles of vapor compression refrigeration, an ASHP uses a refrigerant system involving a compressor and a condenser to absorb heat at one place and release it at another. They can be used as a space heater or cooler, and are sometimes called "reverse-cycle air conditioners".

In domestic heating use, an ASHP absorbs heat from outside air and releases it inside the building, as hot air, hot water-filled radiators, underfloor heating and/or domestic hot water supply. The same system can often do the reverse in summer, cooling the inside of the house. When correctly specified, an ASHP can offer a full central heating solution and domestic hot water

Central Air Conditioner Heat Pump Parameter

A7W35 working condition: inlet air temperature 7℃, outlet water temperature 35℃

a: Nominal heating conditions: ambient dry bulb temperature-12℃, wet bulb temperature-14℃, outlet water temperature 41℃, water flow 0.172 * nominal

Model SLNA-032Y SLNB-047Y SLNC-075Y
Compressor capacity 10HP 15HP 25HP
Function Heating and Cooling Heating and Cooling Heating and Cooling
Electricity 380V-3N-50Hz 380V-3N-50Hz 380V-3N-50Hz
Working conditions -25~+45 -25~+45 -25~+45
Data Heata Nominal capacity KW 21.5 28.1 44.5
Input power KW 9.1 11.7 18.3
COP / 2.3 2.4 2.4
Heating IPLV(H) 2.7 2.7 2.7
Coolb Nominal capacity KW 25 39 62
Input power KW 10 13.1 20.7
COP / 2.5 2.9 3
Cooling IPLV(C) 2.7 2.7 2.7
A7W35c KW/COP 32.0/4.1 47.0/4.1 75.0/4.2
A2W35 KW/COP 27/3.60 39.5/3.20 62.5/3.20
A-7W35 KW/COP 21.5/2.8 32/2.9 50/2.9
A-15W55 KW/COP 19.7 /1.94 28.1/1.94 45.5 /1.97
A-20W45 KW/COP 18.1/2.02 23.6/2.03 37.4/2.04
Max. running currency A 25 35 56
Compressor quantity set 2 2 2
Refrigerant/charging quantity kg / R22/3.7*2 R22/10 R22/15*2
Air blow type / Top Top Top
Water pipe diameter mm 32 50 50
Rating flow m³/h 5.5 8.3 12.6
Water side pressure loss kPa ≤45 ≤45 ≤45
Noise level dB(A) 62 62 62
Overall dimensions(L×W×H) mm 1530×750×1370 1450×1100×2080 2100×1100×2080
Weight kg 320 470 730

Our service

  • Central control system, automatic and easy operation
  • Inquiry reply within 24hours
  • fast delivery 1-2 weeks
Inquiry Cart 0