Add to Cart
Heating And Cooling Heat Pump Heating And Cooling System For Home Use
Project Introduction
Location: Heibei province
Greenhouse area: 2000 sqm
Function: In summer cooling; in winter heating supplement for solar energy greenhouse.
Project function: Ecological agriculture sightseeing greenhouse
Advantages: Energy saving, zero pollution, solve low temeprature problem of greenhouse in winter
Yushen Heat Pump Features
Technical data
Compressor brand: Copeland
Water side heat exchanger: shell and tube type
Air side heat exchanegr: inner thread copper tube and Hydrophilic aluminum foils
| Model | SLNC-075Y | |||
| Compressor capacity | 25HP | |||
| Function | Heating and Cooling | |||
| Electricity | 380V-3N-50Hz | |||
| Working conditions | ℃ | -25~+45 | ||
| Data | Heata | Nominal capacity | KW | 44.5 |
| Input power | KW | 18.3 | ||
| COP | / | 2.4 | ||
| Heating IPLV(H) | 2.7 | |||
| Coolb | Nominal capacity | KW | 62 | |
| Input power | KW | 20.7 | ||
| COP | / | 3 | ||
| Cooling IPLV(C) | 2.7 | |||
| A7W35c | KW/COP | 75.0/4.2 | ||
| A2W35 | KW/COP | 62.5/3.20 | ||
| A-7W35 | KW/COP | 50/2.9 | ||
| A-15W55 | KW/COP | 45.5 /1.97 | ||
| A-20W45 | KW/COP | 37.4/2.04 | ||
| Max. running currency | A | 56 | ||
| Compressor quantity | set | 2 | ||
| Refrigerant/charging quantity kg | / | R22/15*2 | ||
| Air blow type | / | Top | ||
| Water pipe diameter | mm | 50 | ||
| Rating flow | m³/h | 12.6 | ||
| Water side pressure loss | kPa | ≤45 | ||
| Noise level | dB(A) | 62 | ||
| Overall dimensions(L×W×H) | mm | 2100×1100×2080 | ||
| Weight | kg | 730 | ||
Tested conditions:
a:Nominal Cooling conditions: ambient dry bulb temperature35℃, , outlet water temperature 7℃, water flow 0.172 * nominal cooling capacity
b:A7W35 working condition: inlet air temperature 7℃, outlet water temperature 35℃
Other applications
Air source heat pump could aslo work as the outdoor unit for Air conditioning of,
Product Certificates